Model: MPA-600
Continuously monitoring the pH value is a crucial step for chemical supervision. Its measurement accuracy and reliability play a vital role in preventing system corrosion and scaling as well as expanding its service life, ensuring system safety, and economic operation.
Measuring range: pH: 0~14.00pH, Resolution:0.01pH
Temperature: 0~100℃, Resolution:0.3℃
Auto temp compensation range: 0~100℃(standard: 25℃)
Sample water: 0~100℃, 0.3MPa
Stability: ±0.02pH/24h
linearity: ±0.03Ph
Repeatability: ±0.02pH
Input impedance: ≥1012 Ω
Current isolation output: 4~20mA
Error of output current: ≤±0.5%FS
Protection grade: IP65
Operation conditions: Ambient temperature: 0~60℃
Relative humidity: <85%
It is mainly used for continuously monitoring and controlling the pH and ORP value of soft water, steam condensation, sea water distillation, raw water and deionized water. It is widely applicable to the pharmacy, sanitation, food, municipal utility, power, and petrochemical industry.